  1.     SECTION 07211
  2.  
  3.     SPRAYED FOAM INSULATION FOR BUILDING ENVELOPE
  4.  
  5. NOTE ** Foam Enterprises sprayed polyurethane foam insulation for building envelope insulation.
  6. NOTE ** 
  7. NOTE ** This section is based on the products of Foam Enterprises, Inc., which is located at:
  8. NOTE **    13630 Water Tower Circle
  9. NOTE **    Minneapolis, MN  55441
  10. NOTE **    Tel:  (800) 888-3342
  11. NOTE **    Fax:  (612) 559-0945
  12. NOTE ** 
  13. NOTE ** This section covers the foam insulation and vapor retarder, plus optional thermal barrier (fire resistive) coating or other material.  This section should not be used for cold storage facility insulation -- use Section 07212 instead.  For sprayed foam roofing, use Section 07570.
  14. NOTE ** 
  15. NOTE ** This specification is based on the following publication of the Society of the Plastics Industry, Inc., Spray Polyurethane Foam Division:
  16. NOTE ** 
  17. NOTE ** "Spray Polyurethane Foam Systems for Building Envelope Insulation and Air Seal; copyright 1994.
  18. NOTE ** 
  19. NOTE ** SECTION 07211 - SPRAYED FOAM INSULATION FOR BUILDING ENVELOPE, Copyright 1997, The Architect's Catalog, Inc.
  20.  
  21. PART 1    GENERAL
  22.  
  23. 1.1    SECTION INCLUDES
  24. NOTE ** Edit items below as required for project.
  25.  
  26.     A.    Sprayed polyurethane foam insulation.
  27.  
  28.     B.    Vapor retarder.
  29.  
  30.     C.    Thermal barrier (fire resistive) coating.
  31.  
  32. 1.2    RELATED SECTIONS
  33. NOTE ** Delete any sections below not relevant to this project; add others as required.
  34.  
  35.     A.    Section 07260 - Vapor Retarders:  Separate sheet vapor retarders.
  36. NOTE ** Roof Decks:  This section should not be used to specify foam insulation on the exterior side of a roof -- use a true foam roofing specification for that.
  37.  
  38.     B.    Section 07570 - Coated Foamed Roofing:  Spray polyurethane foam on exterior side of roof decks.
  39.  
  40.     C.    Section 09260 - Gypsum Board Assemblies:  Gypsum board for thermal barrier covering foam insulation.
  41.  
  42.     D.    Division 15 - Mechanical:  Plumbing and HVAC components penetrating insulation.
  43.  
  44.     E.    Division 16 - Electrical:  Electrical components penetrating insulation.
  45.  
  46. 1.3    REFERENCES
  47. NOTE ** Add any references to the list below that are included in text you have added to the section.
  48.  
  49.     A.    ASTM D 1621 - Standard Test Method for Compressive Properties of Rigid Cellular Plastics.
  50.  
  51.     B.    ASTM D 1622 - Standard Test Method for Apparent Density of Rigid Cellular Plastics.
  52.  
  53.     C.    ASTM D 2856 - Standard Test Method for Open-Cell Content of Rigid Cellular Plastics by the Air Pycnometer.
  54.  
  55.     D.    ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
  56.  
  57.     E.    ASTM E 96 - Standard Test Methods for Water Vapor Transmission of Materials.
  58.  
  59.     F.    SPI Bulletin AX-119 - MDI-Based Polyurethane Foam Systems: Guidelines for Safe Handling and Disposal; Society of the Plastics Industry, Inc., Polyurethane Division.
  60.  
  61. 1.4    SUBMITTALS
  62. NOTE ** Delete types of submittals not required.  Coordinate submittal statements with other provisions in the section.
  63.  
  64.     A.    Submit under provisions of Section 01300.
  65.  
  66.     B.    Product Data:  Manufacturer's data on products to be installed.
  67.         1.    Application or installation instructions.
  68.         2.    Listing, classification, and approval certifications.
  69.         3.    Safety and handling instructions for storage, handling and use of the materials.
  70.  
  71.     C.    Product Certification:  SPI/SPDF accreditation test for materials.
  72.  
  73.     D.    Certifications:  If manufacturer's published data sheets do not indicate compliance with all specification requirements, provide letter of certification that all products comply with the specification requirements; include primers (if required), foam and coatings.
  74.  
  75.     E.    Shop Drawings:  Show materials and details of fabrication of sheet metal, accessories, or other fabricated items.
  76.  
  77.     F.    Qualification Statements:
  78.         1.    Manufacturer qualifications.
  79.         2.    Installer qualifications.
  80.         3.    Independent inspector qualifications.
  81.  
  82.     G.    Applicator's Field Quality Control Procedures:  Written description of procedures to be utilized to insure proper preparation and installation of foam and coatings, detail work and follow-up inspection.
  83.  
  84.     H.    Maintenance Data:  Manufacturers' recommended protection, cleaning, and repair procedures, including recommended frequency of inspection.
  85.  
  86. 1.5    QUALITY ASSURANCE
  87.  
  88.     A.    Installer Qualifications:  A firm with experience installing insulation systems of the type specified.
  89. NOTE ** Delete the following paragraph if not required.
  90. NOTE ** 
  91. NOTE ** The Society of the Plastics Industry Spray Polyurethane Foam Division conducts an Accreditation Program for improvement of quality in the application of spray polyurethane foams and coatings.
  92. NOTE ** 
  93. NOTE ** The list of accredited individuals and firms is available from SPFD.
  94.         1.    Show contractor/supplier level accreditation by SPI SPFD Accreditation Program.
  95.         2.    Approved or certified by the foam manufacturer as qualified to install the specified system.
  96.         3.    Provide information concerning projects similar in nature to the one proposed including location and person to be contacted. 
  97.  
  98. 1.6    DELIVERY, STORAGE, AND HANDLING
  99.  
  100.     A.    Provide materials packaged in the manufacturer's original, tightly sealed containers or unopened packages, clearly labelled with the manufacturer's name, product identification, safety information, and batch or lot numbers where appropriate.  Where materials are covered by a referenced specification, the labels shall bear the specification number, type and class, as applicable.
  101.  
  102.     B.    Store materials out of the weather and out of direct sunlight in locations where the temperatures are within the limits specified by the manufacturer.
  103.  
  104. 1.7    PROJECT CONDITIONS
  105. NOTE ** Normally safety procedures are the responsibility of the contractor.  For more information about polyurethane foam see SPI Bulletin AX-119, "MDI-Based Polyurethane Foam Systems: Guidelines for Safe Handling and Disposal."
  106.  
  107.     A.    Comply with the manufacturer's instructions and recommendations as to handling and safety procedures.
  108.  
  109. PART 2    PRODUCTS
  110.  
  111. 2.1    MANUFACTURERS
  112.  
  113.     A.    Provide products of Foam Enterprises, Inc., 13630 Water Tower Circle, Minneapolis, MN 55441. ASD. Tel: (800) 888-3342. Fax: (612) 559-0945.
  114.  
  115.     B.    Substitutions are not acceptable.
  116. NOTE ** Delete paragraph above or below.  Edit Section Number as required for project.
  117.  
  118.     C.    Submit requests for substitutions in accordance with provisions of Section 01600.
  119.  
  120. 2.2    MATERIALS
  121. NOTE ** Most published data is run on laboratory produced samples, not in-place material.  The thickness of polyurethane foam sprayed, number of passes, temperature of substrate, ambient temperatures, etc., all affect properties.  The following values are for Foam Enterprises' product in-place.
  122.  
  123.     A.    Foam:  Sprayed-in-place two-component closed-cell polyurethane made by combining an isocyanate (A) component with a polyol (B) component, with the following physical characteristics:
  124.         1.    Density in place, when tested in accordance with ASTM D 1622:  1.7 to 1.8 lb/cu ft (27 to 29 kg/cu m).
  125.         2.    Compressive Strength, when tested in accordance with ASTM D 1621:  20 to 30 psi (1.4 to 2.1 Pa), minimum.
  126.         3.    Closed Cell Content, when tested in accordance with ASTM D 2856:  87 percent, minimum.
  127.         4.    R-value, aged:  6.8.
  128. NOTE ** From a fire safety standpoint, polyurethane foams can be used safely. It is important, however, that all persons associated with the design, fabrication, storage and installation understand the materials and environments involved.
  129. NOTE ** 
  130. NOTE ** Polyurethane foam insulation is combustible and should be treated as such. Flame spread ratings provided for polyurethane products using small scale tests are not intended to reflect the hazards presented by this or any other materials under actual fire conditions. Care must be taken to ensure that the foam is not exposed to heat or flame.
  131.         5.    Flame Spread Index, when tested in accordance with ASTM E 84:  Less than 75.
  132.         6.    Smoke Developed Index, when tested in accordance with ASTM E 84: Less than 450.
  133.  
  134.     B.    Primers:  As recommended by the manufacturer of the spray foam materials specified.
  135. NOTE ** The following paragraph is for a vapor retarder coating to be applied directly to the foam.  If the foam is to be covered by other construction, such as gypsum drywall, other types of vapor barriers can be used -- specify them in another section.
  136.  
  137.     C.    Vapor Retarder:  Fluid-applied coating, Lion Oil Co., Nokorde 706M; permeability of 0.01 perm or less, when tested in accordance with ASTM E 96, Method D.
  138. NOTE ** A thermal barrier (fire resistive) is almost always required over polyurethane foam exposed on the interior of the building.  Typically, the minimum thermal barrier is a material that constitutes 15 minutes of fire protection for the foam.  Materials that have been used include sprayed cementitious or fiber material (such as fireproofing) and gypsum board.
  139. NOTE ** 
  140. NOTE ** Delete the following paragraph if the thermal barrier is not a coating and is specified in another section.
  141.  
  142.     D.    Thermal Barrier:  Sprayed coating, W.R. Grace Zonolite 3306 or International Cellulose Ure-K; applied for fire resistance rating of 15 minutes.
  143.  
  144. PART 3    EXECUTION
  145.  
  146. 3.1    GENERAL
  147.  
  148.     A.    Comply with the instructions and recommendations of the foam and coatings manufacturers.
  149.  
  150.     B.    Familiarize all installers with correct and safe application and handling procedures:
  151.         1.    See SPI Bulletin AX-119, "MDI-Based Polyurethane Foam Systems: Guidelines for Safe Handling and Disposal."
  152.         2.    Refer to appropriate Materials Safety Data Sheets (MSDS) for additional safety information.
  153.  
  154. 3.2    PREPARATION
  155.  
  156.     A.    Primed Steel:  If the surface is free of loose scale, rust, weathered or chalking paint, it can be cleaned using vacuum equipment and hand or power tools to remove loose dirt.
  157.  
  158.     B.    Previously Painted Steel:  Clean using hand or power tools to remove loose scale and dirt.
  159.  
  160.     C.    Galvanized Steel and Unpainted Steel:  Clean as recommended by primer manufacturer.
  161.  
  162.     D.    New Concrete:  Allow to cure for twenty-eight (28) days prior to the application of primer or foam.
  163.  
  164.     E.    Previously Painted Surfaces:  Remove all loose paint.
  165.  
  166.     F.    Remove loose dirt, dust and debris by using compressed air, vacuum equipment or brooming.  Remove oil, grease, form release agents, laitance, and other contaminants using proper cleaning solutions.  Do not wash wood or porous materials with water.
  167.  
  168.     G.    Grout, tape, or calk all joint openings that exceed 1/4 inch (6 mm) in width.
  169.  
  170.     H.    Prime all metal as recommended by manufacturer.
  171.  
  172.     I.    Prime all concrete surfaces.
  173.  
  174. 3.3    FOAM APPLICATION
  175.  
  176.     A.    Do not begin application of foam until all preparation requirements have been completed.
  177.  
  178.     B.    Do not apply foam when the temperature is below or the humidity is above that specified by the manufacturer for ambient air and substrate.
  179.  
  180.     C.    Apply foam in accordance with the manufacturer's specifications and instructions.
  181.  
  182.     D.    Apply foam to a ____ inch (____ mm) thickness, with pass thickness of 1/2 inch (13 mm) to 1-1/2 inches (38 mm).  Complete the full thickness of foam in any area prior to the end of each day.
  183. NOTE ** The following article is for vapor retarder coating.  Delete if a sheet-type vapor retarder is used.
  184.  
  185. 3.4    VAPOR RETARDER INSTALLATION
  186.  
  187.     A.    Apply vapor retarder in accordance with building code requirements and the manufacturer's specifications and instructions.
  188.  
  189.     B.    Apply vapor retarder to the entire surface of the foam in a continuous film across corners and junctions.
  190. NOTE ** Delete the following article if the thermal barrier is not a spray-applied coating.
  191.  
  192. 3.5    THERMAL BARRIER APPLICATION
  193.  
  194.     A.    Allow vapor retarder to cure before the thermal barrier coating is applied.  Repair damage and defects to the vapor retarder prior to the application of the thermal barrier.
  195.  
  196.     B.    Apply thermal barrier over entire surface of foam.
  197.  